Goodrive350 IP55 High-ingress Protection Series VFD
Function parameter list
-182-
Function
code
Name
Description
Default
value
Modify
0: Act during undervoltage fault
1: Do not act during undervoltage fault
Tens:
0: Act during fault reset
1: Do not act during fault reset
P11.14
Speed
deviation
detection
value
0.0
–50.0%
This parameter is used to set the speed deviation
detection value.
10.0%
○
P11.15
Speed
deviation
detection time
0.0
–10.0s
This parameter is used to set the speed deviation
detection time.
Note:
Speed deviation protection will be invalid if
is set to 0.0.
Speed
Actual detection
value
Set detection
value
Time t
t1
t2
t2=P11.15
t1<t2, so the VFD continues running
dEu
Running
Fault output
Setting range: 0.0
–10.0s
2.0s
○
P11.16
Automatic
frequency-red
uction during
voltage drop
0
–1
0: Invalid
1: Valid
0
○
P11.17
Proportional
coefficient of
voltage
regulator
during
undervoltage
stall
0
–1000
100
○
P11.18
Integral
coefficient of
voltage
regulator
during
undervoltage
stall
0
–1000
40
○
P11.19
Proportional
coefficient of
current
regulator
0
–1000
25
○