Goodrive350 IP55 High-ingress Protection Series VFD
Basic Operation Instructions
-102-
When frequency command selection (P00.06, P00. 07) is 7, or channel of voltage setup
(P04.27) is 6, the running mode of VFD is process PID control.
5.5.15.1 General procedures for PID parameter setup
a. Determining proportional gain P
When determining proportional gain P, first, remove the integral term and derivative term of
PID by making Ti=0 and Td=0 (see PID parameter setup for details), thus turning PID into pure
proportional control. Set the input to 60%
–70% of the max. allowable value, and increase
proportional gain P gradually from 0 until system oscillation occurred, and then in turn,
decrease proportional gain P gradually from current value until system oscillation disappears,
record the proportional gain P at this point and set the proportional gain P of PID to 60%
–70%
of current value. This is whole commissioning process of proportional gain P.
b. Determine integral time Ti
After proportional gain P is determined, set the initial value of a larger integral time Ti, and
decrease Ti gradually until system oscillation occurred, and then in turn, increase Ti until
system oscillation disappears, record the Ti at this point, and set the integral time constant Ti of
PID to 150%
–180% of current value. This is the commissioning process of integral time
constant Ti.
c. Determining derivative time Td
The derivative time Td is generally set to 0.
If users need to set Td to another value, set in the same way with P and Ti, namely set Td to 30%
of the value when there is no oscillation.
d. Empty system load, perform load-carrying joint debugging, and then fine-tune PID
parameter until fulfilling the requirement.
5.5.15.2 How to fine-tune PID
After setting the parameters controlled by PID, users can fine-tune these parameters by the
following means.
Control overmodulation:
When overmodulation occurred, shorten the derivative time (Td)
and prolong integral time (Ti).
Before adjustment
After adjustment
Response
Time t
Stabilize the feedback value as fast as possible:
when overmodulation occurred, shorten
integral time (Ti) and prolong derivative time (Td) to stabilize control as fast as possible.