Goodrive350 IP55 High-ingress Protection Series VFD
Function parameter list
-181-
Function
code
Name
Description
Default
value
Modify
alarm, and stops running after overload fault.
2: The VFD continues running after overload
alarm, and stops running after underload fault.
3: The VFD stops running after overload/underload
fault.
Hundreds place:
0: Always detect
1: Detect during constant-speed running
Thousands place: VFD overload current reference
selection
0: Related to current calibration coefficient
1: Irrelated to current calibration coefficient
P11.09
Overload
pre-alarm
detection level
If the VFD or motor output current is larger than
the overload pre-alarm detection level (P11.09),
and the duration exceeds the overload pre-alarm
detection time (P11.10), overload pre-alarm signal
will be outputted.
Y,
RO1, RO2
Output current
Overload pre-alarm
threshold
Time t
Time t
Pre-alarm time t
Pre-alarm time t
Setting range of P11.09: P11.11
–200% (relative
value determined by the ones place of P11.08)
Setting range of P11.10: 0.1
–3600.0s
G model:
150%
P model:
120%
○
P11.10
Overload
pre-alarm
detection time
1.0s
○
P11.11
Underload
pre-alarm
detection level
Underload pre-alarm signal will be outputted if the
output current of the VFD or motor is lower than
underload pre-alarm detection level (
), and
the
duration
exceeds
underload
pre-alarm
detection time (
Setting range of
: 0
– P11.09 (relative value
determined by the ones place of P11.08)
Setting range of
: 0.1
–3600.0s
50%
○
P11.12
Underload
pre-alarm
detection time
1.0s
○
P11.13
Fault output
terminal action
during fault
This function code is used to set the action of fault
output terminals during undervoltage and fault
reset.
0x00
–0x11
Ones:
0x00
○