Goodrive350 IP55 High-ingress Protection Series VFD
Function parameter list
-141-
Function
code
Name
Description
Default
value
Modify
coefficient after
autotuning
control mode for synchronous motors, you can
set the value of this function code to P03.09.
Range: 0
–65535
Note:
Set the value to 0 if motor parameter
autotuning is not performed.
P03.46
Current integral
proportional
coefficient after
autotuning
Automatic update will be performed after motor
parameter autotuning. In the closed-loop vector
control mode for synchronous motors, you can
set the value of this function code to P03.10.
Range: 0
–65535
Note:
Set the value to 0 if motor parameter
autotuning is not performed.
0
●
P04
––V/F control
Function
code
Name
Description
Default
value
Modify
P04.00
V/F curve setup
of motor 1
This group of function code defines the V/F
curve of motor 1 to satisfy different load
characteristics needs.
0: Straight V/F curve; fit for constant-torque load
1: Multi-point V/F curve
2: Torque down V/F curve (power of 1.3)
3: Torque down V/F curve (power of 1.7)
4: Torque down V/F curve (power of 2.0)
Curve 2
–4 are suitable for torque-variable load
of fan pump and similar equipment. Users can
make adjustment based on load characteristics
to achieve optimal energy-saving effect.
5: Customized V/F (V/F separation); under this
mode, V is separated from f. Users can adjust f
through the frequency reference channel set by
to change the curve characteristic, or
adjust V through the voltage reference channel
set
by
to
change
the
curve
characteristics.
Note: The V
b
in the figure below corresponds to
rated motor voltage, and
f
b
corresponds to rated
motor frequency.
Output voltage
Output frequency
Linear type
Square type
Torque step-down V/F curve (power of 1.3)
Torque step-down V/F curve (power of 1.7)
Torque step-down V/F curve (power of 2.0)
0
◎