Goodrive350 IP55 High-ingress Protection Series VFD
Function parameter list
-175-
Function
code
Name
Description
Default
value
Modify
P09.12
Feedback offline
detection time
offline detection value, and the duration exceeds
the value set in
, the VFD will report "PID
feedback offline fault", and keypad displays
PIDE.
T
Output frequency
t1
t2
P09.11
t1
<
T2, so the VFD
continues running
t2=P09.12
Running
Fault output PIDE
PIDE
Setting range of
: 0.0
–100.0%
Setting range of
: 0.0
–3600.0s
1.0s
○
P09.13
PID control
selection
0x0000
–0x1111
Ones:
0: Continue integral control after the frequency
reaches upper/lower limit
1: Stop integral control after the frequency
reaches upper/lower limit
Tens:
0: The same with the main reference direction
1: Contrary to the main reference direction
Hundreds:
0: Limit based on the max. frequency
1: Limit based on A frequency
Thousands:
0: A+B frequency, acceleration /deceleration of
main reference A frequency source buffering is
invalid
1: A+B frequency, acceleration/ deceleration of
main reference A frequency source buffering is
valid, acceleration and deceleration are
determined by
0x0001
○
P09.14
Low-frequency
proportional gain
(Kp)
0.00
–100.00
Low-frequency switching point: 5.00Hz,
high-frequency switching point: 10.00Hz
(
corresponds to high-frequency
parameter), and the middle is the linear
interpolation between these two points
1.00
○
P09.15
Acceleration/
deceleration
time of PID
command
0.0
–1000.0s
0.0s
○
P09.16
Filter time of PID
output
0.000
–10.000s
0.000s
○
P09.17
Reserved
-100.0
–100.0%
0.0%
○