ILVFE-series
user manual
67
Common symptoms and corrective action
Motor does not start
Cause(s)
Indication
Corrective action
No output voltage to the
motor.
None
•
Check the power circuit.
•
Check the supply voltage.
•
Check all fuses and disconnects.
•
Check the motor.
•
Verify that the motor is connected properly.
Check the control input signals.
•
Verify that a Start signal is present. If 2-Wire
control is used, verify that either the Run
Forward or Run Reverse signal is active, but
not both.
•
Verify that I/O Terminal 01 is active.
•
Verify that P106 [Start source] matches your
configuration.
•
Verify that A434 [Reverse disable] is not
prohibiting movement.
Improper boost setting at initial
start-up
None
Set A453 [Boost Select] to option 2 “35.0, VT”.
Drive is faulted
Flashing red
status light
•
Clear fault.
•
Press stop.
•
Cycle power.
•
Set A450 [Fault clear] to option 1 “Clear faults”.
•
Cycle digital input if t201 - t202 [Digital inx sel]
is set to option 7 “Clear fault”.
Drive does not start from integral keypad.
Cause(s)
Indication
Corrective action
Integral keypad is not enabled
Green LED
above start key
is not
illuminated.
•
Set parameter P106 [Start source] to option 0
“Keypad”.
•
Set parameter t201 - t202 [Digital inx select] to
option 5 “Local” and activate the input.
I/O terminal 01 "Stop" input is
not present
None
Wire inputs correctly and/or install jumper.
Содержание ILVFE-1W0075
Страница 1: ......
Страница 2: ...2 ILVFE series user manual...
Страница 23: ...ILVFE series user manual 23...
Страница 74: ...74 ILVFE series user manual Product dimensions Frame A Frame B Frame C...
Страница 75: ...ILVFE series user manual 75 Recommended external brake resistor circuitry External display optional...
Страница 79: ...ILVFE series user manual 79 Additional information More info can be found on our website www indulogix com...
Страница 80: ...80 ILVFE series user manual...
Страница 81: ......