ILVFE-series
user manual
53
A424 [DC brake time]
Related Parameter(s): P107, A425
Sets the length of time that DC brake current is “injected” into the motor. Refer to parameter A425 [DC
brake level].
Values
Default:
0.0 Secs
Min/Max:
0.0/99.9 Secs (a setting of 99.9= continous)
Display:
0.1 Secs
A425 [DC brake level]
Related Parameter(s): P107, A418
Defines the maximum DC brake current, in amps, applied to the motor when P107 [Stop Mode] is set
to either “Ramp” or “DC Brake”.
Values
Default:
Drive rated amps x 0.05
Min/Max:
0.0/(Drive rated amps x 1.8)
Display:
0.1 Amps
Attention:
If a hazard of injury due to movement of equipment or material exists, an
auxiliary mechanical braking device must be used.
Attention:
This feature should not be used with synchronous or permanent magnet
motors. Motors may be demagnetized during braking.
Содержание ILVFE-1W0075
Страница 1: ......
Страница 2: ...2 ILVFE series user manual...
Страница 23: ...ILVFE series user manual 23...
Страница 74: ...74 ILVFE series user manual Product dimensions Frame A Frame B Frame C...
Страница 75: ...ILVFE series user manual 75 Recommended external brake resistor circuitry External display optional...
Страница 79: ...ILVFE series user manual 79 Additional information More info can be found on our website www indulogix com...
Страница 80: ...80 ILVFE series user manual...
Страница 81: ......