ILVFE-series
user manual
49
C305 [Comm loss time]
Related Parameter(s): d015, C304
Sets the time that the drive will remain in communication loss before implementing the option selected
in C304 [Comm loss action].
Values
Default:
5.0 Secs
Min/Max:
0.1/60.0 Secs
Display:
0.1 Secs
C306 [Comm format]
Selects the protocol (RTU only), data bits (8 data bits only), parity (None, Even, Odd), and stop bits
(1 stop bit only) used by the RS485 port on the drive.
Refer to Appendix C for details on using the drive communication features.
Important:
Power to drive must be cycled before any changes will affect drive operation.
Options 0
"
RTU 8-N-1" (Default)
1
"RTU 8-E-1"
2
"RTU 8-O-1"
3
"RTU 8-N-2"
4
"RTU 8-E-2"
5
"RTU 8-O-2"
C307 [Comm write mode]
Determines whether parameter changes made over communication port are saved and stored in Non-
Volatile Storage (NVS) or RAM only. If they are stored in RAM, the values will be lost at power-down.
Options
0
"Save" (Default)
1
"RAM only"
Attention:
Risk of equipment damage exists. If a controller is programmed to write
parameter data to Non-Volatile Storage (NVS) frequently, the NVS will quickly
exceed its life cycle and cause the drive to malfunction.
Do not create a program that frequently uses configurable outputs to write
parameter data to NVS unless C307 [Comm write mode] is set to option 1.
Содержание ILVFE-1W0075
Страница 1: ......
Страница 2: ...2 ILVFE series user manual...
Страница 23: ...ILVFE series user manual 23...
Страница 74: ...74 ILVFE series user manual Product dimensions Frame A Frame B Frame C...
Страница 75: ...ILVFE series user manual 75 Recommended external brake resistor circuitry External display optional...
Страница 79: ...ILVFE series user manual 79 Additional information More info can be found on our website www indulogix com...
Страница 80: ...80 ILVFE series user manual...
Страница 81: ......