48
ILVFE-series
user manual
Communications group
C301 [Language]
Selects the language displayed by the remote communications option.
Options
1
"English" (Default)
2
"Second language" (Reserved)
C302 [Comm data rate]
Related Parameter(s): d015
Sets the serial port rate for the RS485 (DSI) port.
Important:
Power to drive must be cycled before changes will affect drive operation.
Options
0
1200 Baud
1
2400 Baud
2
4800 Baud
3
9600 Baud (Default)
4
19.2k Baud
5
38.4k Baud
C303 [Comm node addr]
Related Parameter(s): d015
Sets the drive node address for the RS485 (DSI) port if using a network connection.
Important:
Power to drive must be cycled before any changes will affect drive operation.
Values
Default:
100
Min/Max:
1/247
Display:
1
C304 [Comm loss action]
Related Parameter(s): d015, P107, C305
Selects the drive’s response to a loss of the communication connection or excessive communication
errors.
Options 0
"Fault" (Default)
Drive will fault on an F81 Comm Loss and coast to stop.
1
"Coast to stop"
Stops drive via coast to stop.
2
"Stop"
Stops drive via P107 [Stop Mode] setting.
3
"Continue last"
Drive continues operating at communication commanded speed
saved in RAM.
Содержание ILVFE-1W0075
Страница 1: ......
Страница 2: ...2 ILVFE series user manual...
Страница 23: ...ILVFE series user manual 23...
Страница 74: ...74 ILVFE series user manual Product dimensions Frame A Frame B Frame C...
Страница 75: ...ILVFE series user manual 75 Recommended external brake resistor circuitry External display optional...
Страница 79: ...ILVFE series user manual 79 Additional information More info can be found on our website www indulogix com...
Страница 80: ...80 ILVFE series user manual...
Страница 81: ......