ILVFE-series
user manual
51
A403 [S curve %]
Sets the percentage of acceleration or deceleration time that is applied to the ramp as S Curve. Time
is added, 1/2 at the beginning and 1/2 at the end of the ramp.
Values
Default:
0% (disabled)
Min/Max:
0/100%
Display:
1%
A404 [Jog frequency]
Related Parameter(s): P105, t201, t202, A405
Sets the output frequency when a jog command is issued.
Values
Default:
10.0 Hz
Min/Max:
0.0/P105 [Maximum freq]
Display:
0.1 Hz
A405 [Jog accel/decel]
Related Parameter(s): t201, t202, A404
Sets the acceleration and deceleration time when a jog command is issued.
Values
Default:
10.0 Secs
Min/Max:
0.1/600.0 Secs
Display:
0.1 Secs
A409 [Internal freq]
Related Parameter(s): P108
Provides the frequency command to the drive when P108 [Speed Reference] is set to 1 “Internal
Freq”. When enabled, this parameter will change the frequency command in “real time” using the
integral keypad Up Arrow or Down Arrow when in program mode.
Important:
Once the desired command frequency is reached, the Enter key must be pressed to store
this value to EEPROM memory. If the ESC key is used before the Enter key, the frequency will return
to the original value following the normal accel/decel curve.
Values
Default:
60.0 Hz
Min/Max:
0.0/400.0 Hz
Display:
0.1 Hz
Содержание ILVFE-1W0075
Страница 1: ......
Страница 2: ...2 ILVFE series user manual...
Страница 23: ...ILVFE series user manual 23...
Страница 74: ...74 ILVFE series user manual Product dimensions Frame A Frame B Frame C...
Страница 75: ...ILVFE series user manual 75 Recommended external brake resistor circuitry External display optional...
Страница 79: ...ILVFE series user manual 79 Additional information More info can be found on our website www indulogix com...
Страница 80: ...80 ILVFE series user manual...
Страница 81: ......