ILVFE-series
user manual
43
Terminal block group
t201 [Digital in1 sel]
(I/O terminal 5)
t202 [Digital in2 sel]
(I/O terminal 6)
Related Parameter(s):d012, d014, P108, P109, P110, t211-t214, A401, A402, A404, A405, A410-413
Selects the function for the digital inputs. Refer to the flowchart in chapter 1 for more information on
speed reference control priority.
Options
0
“Not used"
Terminal has no function but can be read over network
communications via d014 [Dig in Status]
1
“Acc 2 & Dec 2”
When active, A401 [Accel Time 2] and A402 [Decel Time 2] are
used for all ramp rates except Jog.
Can only be tied to one input.
Refer to the flowchart in chapter 1 for more information on
Accel/Decel selection.
2
“Jog”
When input is present, drive accelerates according to the value set
in A405 [Jog Accel/Decel] and ramps to the value set in A404 [Jog
Frequency].
When input is removed, drive ramps to a stop according to the
value set in A405 [Jog Accel/Decel].
A valid “Start” command will override this input.
3
“Aux fault”
When enabled, an F2 Auxiliary Input fault will occur when the input
is removed.
4
“Preset
Freq”(default)
External frequency command as defined by A410 - A413 [Preset
Freq x] when t201 and t202 [Digital Inx Sel] are programmed as
“Preset Frequencies” and the digital inputs are active.
5
"local"
When active, sets integral keypad as start source and
potentiometer on the integral keypad as speed source.
6
"Comm port"
When active, sets communications device as default start/speed
command source.
Can only be tied to one input.
7
"Clear fault"
When active, clears an active fault
8
"Rampstop, CF"
Causes drive to immediately ramp to a stop regardless of how P107
[Stop Mode] is set.
9
"Coaststop, CF"
Causes drive to immediately coast to a stop regardless of how
P107 [Stop Mode] is set.
10
"DCinjstop, CF"
Causes drive to immediately begin a DC Injection stop regardless of
how P107 [Stop Mode] is set.
11
"Jog forward"
Drive accelerates to A404 [Jog Frequency] according to A405 [Jog
Accel/Decel] and ramps to stop when input becomes inactive. A
valid start will override this command.
Stop drive before changing this parameter
Содержание ILVFE-1W0075
Страница 1: ......
Страница 2: ...2 ILVFE series user manual...
Страница 23: ...ILVFE series user manual 23...
Страница 74: ...74 ILVFE series user manual Product dimensions Frame A Frame B Frame C...
Страница 75: ...ILVFE series user manual 75 Recommended external brake resistor circuitry External display optional...
Страница 79: ...ILVFE series user manual 79 Additional information More info can be found on our website www indulogix com...
Страница 80: ...80 ILVFE series user manual...
Страница 81: ......