78
ILVFE-series
user manual
Reading (03) and Writing (06) drive parameters
Modbus Adress
8192
(Logic command) can be used to control the ILVFE drive. In addition to being
written (with Function code 06 or 16), register address 8192 can be read using Function code 03.
Adress (decimal)
Bit(s)
Description
8192
0
1 = Stop, 0 = Not stop
1
1 = Start, 0 = Not start
2
1 = Jog, 0 = Not jog
3
1 = Clear faults, 0 = No faults
4,5
00 = No command
01 = Forward command
10 = Reverse command
11 = No command
6
Not used
7
Not used
8,9
00
=
No command
01
=
Accel rate 1 enable
10
=
Accel rate 2 enable
11 = Hold Accel rate select
10,11
00
=
No command
01
=
Decel rate 1 enable
10
=
Decel rate 2 enable
11 = Hold Decel rate select
12, 13, 14
000
=
No command
001
=
Freq Source= P108[Speed reference]
010
=
Freq Source= A409[Internal freq]
011
=
Freq Source= Comms (Addr 8193)
100
=
A410[Preset freq0]
101
=
A411[Preset freq1]
110
=
A412[Preset freq2]
111
=
A413[Preset freq3]
15
Not used
8193
-
A decimal value entered as xxx.x where the
decimal point is fixed. For example, a decimal
“100” equals 10.0 Hz and “543” equals 54.3 Hz.
To access drive parameters, the Modbus register address equals the parameter number. For example,
a decimal “1” is used to address Parameter d001 [Output Freq] and decimal “109” is used to address
Parameter P109 [Accel Time 1].
Содержание ILVFE-1W0075
Страница 1: ......
Страница 2: ...2 ILVFE series user manual...
Страница 23: ...ILVFE series user manual 23...
Страница 74: ...74 ILVFE series user manual Product dimensions Frame A Frame B Frame C...
Страница 75: ...ILVFE series user manual 75 Recommended external brake resistor circuitry External display optional...
Страница 79: ...ILVFE series user manual 79 Additional information More info can be found on our website www indulogix com...
Страница 80: ...80 ILVFE series user manual...
Страница 81: ......