Chapter 2 - Start up
Preparing the drive start-up
This chapter describes how to start up the ILVFE Drive. To simplify drive setup, the most commonly
programmed parameters are organized in a single Basic Program Group.
Important:
Read the General Precautions section before proceeding.
ATTENTION:
Power must be applied to the drive to perform the following start-up
procedures. Some of the voltages present are at incoming line potential. To avoid
electric shock hazard or damage to equipment, only qualified service personnel
should perform the following procedure. Thoroughly read and understand the
procedure before beginning. If an event does not occur while performing this
procedure,
do not proceed.
Remove all power including user supplied control
voltages. User supplied voltages may exist even when main AC power is not applied
to the drive. Correct the malfunction before continuing.
Before Applying Power to the Drive
1. Confirm that all inputs are connected to the correct terminals and are secure.
2. Verify that AC line power at the disconnect device is within the rated value of the drive.
3. Verify that any digital control power is 24 Volts.
4. Verify that the Sink (SNK)/Source (SRC) Setup DIP Switch is set to match your control wiring
scheme. See Figure 1.5 in Chapter 1 of this manual.
Important:
The default control scheme is Source (SRC). The Stop terminal is jumpered (I/O
Terminals 01 and 11) to allow starting from the keypad. If the control scheme is changed to
Sink (SNK), the jumper must be removed from I/O Terminals 01 and 11 and installed between
I/O Terminals 01 and 04.
5. Verify that the Stop input is present or the drive will not start.
Important:
If I/O Terminal 01 is used as a stop input, the jumper between I/O Terminals 01
and 11 must be removed.
Applying power to the drive.
6. Apply AC power and control voltages to the drive.
7. Familiarize yourself with the integral keypad features before setting any program group
parameters.
Start, Stop, Direction and Speed Control
Factory default parameter values allow the drive to be controlled from the integral keypad. No
programming is required to start, stop, change direction and control speed directly from the integral
keypad.
Important:
To disable reverse operation, see
A434
[Reverse Disable].
If a fault appears on power up, refer to Fault Descriptions on page 66 for an explanation of the fault
code.
Variable Torque Fan/Pump Applications
For improved motor tuning performance when using a premium efficient motor on a variable torque
load, set
A453
[Boost Select] to option 2 “35.0, VT”.
Содержание ILVFE-1W0075
Страница 1: ......
Страница 2: ...2 ILVFE series user manual...
Страница 23: ...ILVFE series user manual 23...
Страница 74: ...74 ILVFE series user manual Product dimensions Frame A Frame B Frame C...
Страница 75: ...ILVFE series user manual 75 Recommended external brake resistor circuitry External display optional...
Страница 79: ...ILVFE series user manual 79 Additional information More info can be found on our website www indulogix com...
Страница 80: ...80 ILVFE series user manual...
Страница 81: ......