ILVFE-series
user manual
57
A442 [Current limit]
Maximum output current allowed before current limiting occurs.
Values
Default:
Drive rated amps x 1.5
Min/Max:
0.1/(Drive rated amps x 1.8)
Display:
0.1 Amps
A444 [Motor OL select]
Related parameter(s): P102, P103
Drive provides Class 10 motor overload protection. Settings 0 – 2 select the derating factor for the l2t
overload function.
Options
0
"No derate" (Default)
1
"Min derate"
2
"Max derate"
A446 [PWM frequency]
Sets the carrier frequency for the PWM output waveform. The chart below provides derating guidelines
based on the PWM frequency setting.
Important:
ignoring derating guidelines can cause reduced drive performance.
Values
Default:
4.0 kHz
Min/Max:
2.0/10.0 kHz
Display:
0.1 kHz