A448 [SW current trip]
Related parameter(s): P103
Enables/disables a software instantaneous (within 100 ms current trip).
Values
Default:
0.0 (Disabled)
Min/Max:
0.0/(Drive rated amps x 2)
Display:
0.1 Amps
A450 [Fault clear]
Resets a fault and clears the fault queue. Used primarily to clear a fault over network communications.
Options
0
"Ready/Idle" (Default)
1
"Reset Fault"
2
"Clear Buffer" (parameters d007-d009 [Fault x code]
A451 [Auto rstrt tries]
Sets the maximum number of times the drive attempts to reset a fault and restart.
Clear a type 1 fault and restart the drive.
1. Set A451[auto rstrt tries] to a value other then "0".
2. Set A452[auto rstrt delay] to a value other then "0".
Clear an overvoltage, undervoltage or heatsink ovrtmp fault without restarting the drive.
1. Set A451[auto rstrt tries] to a value other then "0".
2. Set A452[auto rstrt delay] to "0".
Values
Default:
0
Min/Max:
0/9
Display:
1
Attention:
Equipment damage and/or personal injury may result if this parameter is
used in an inappropriate application. Do not use this function without considering
applicable local, national and international codes, standards, regulations or industry
guidelines.
A451 [Auto rstrt tries]
Related parameter(s): A451
Sets the time between restart attempts when A451 [Auto Rstrt Tries] is set to a value other than zero.
Values
Default:
1.0 Secs
Min/Max:
0.0/120.0 Secs
Display:
0.1 Secs
Stop drive before changing this parameter
Содержание ILVFE-1W0075
Страница 1: ......
Страница 2: ...2 ILVFE series user manual...
Страница 23: ...ILVFE series user manual 23...
Страница 74: ...74 ILVFE series user manual Product dimensions Frame A Frame B Frame C...
Страница 75: ...ILVFE series user manual 75 Recommended external brake resistor circuitry External display optional...
Страница 79: ...ILVFE series user manual 79 Additional information More info can be found on our website www indulogix com...
Страница 80: ...80 ILVFE series user manual...
Страница 81: ......