10
ILVFE-series
user manual
Mounting the unit
Mount the drive upright on a flat, vertical and level surface.
Install on 35mm DIN-Rail (for frames A and B) or install with screws (see table 1.A below).
Table 1.A
Screw mounting recommendations
Minimum Panel Thickness
Screw Size
Mounting Torque
1.9 mm (0.0747 inch.)
M4 (#8-32)
1.56 – 1.96 N-m (14-17 lb. –in)
•
Protect the cooling fan by avoiding dust or metallic particles.
•
Do not expose to a corrosive atmosphere.
•
Protect from moisture and direct sunlight.
Minimum Mounting Clearances
Table 1.B
Horizontal clearance between drives
Ambient Temperature
Minimum
Maximum
0 mm and greater
-10°C (14°F)
40°C (104°F)
25 mm and greater
-10°C (14°F)
50°C (122°F)
Storage
•
Store within an ambient temperature of -40°C to +85°C.
•
Store within a relative humidity range of 0% to 95%, non condensing.
•
Do not expose to corrosive atmosphere.