Table 18. IMM2 error messages (continued)
v
Follow the suggested actions in the order in which they are listed in the Action column until the problem is
solved.
v
If an action step is preceded by “(Trained technician only),” that step must be performed only by a trained
technician.
806f0a07-0301xxxx
806f0a07-0302xxxx
The Processor CPU
n
is operating in a
Degraded State. (
n
=
microprocessor
number)
Warning
Throttling has
occurred for
microprocessor
n
.
(
n
=
microprocessor
number)
1.
Make sure that the fans are
operating, that there are no
obstructions to the airflow (front
and rear of the server), that the air
baffles are in place and correctly
installed, and that the server cover
is installed and completely closed.
2.
Check the ambient temperature. You
must be operating within the
specifications.
3.
Make sure that the heat sink for
microprocessor
n
is installed
correctly.
4.
(Trained technician only) Replace
microprocessor
n
.
(
n
= microprocessor number)
80070201-0301xxxx
80070201-0302xxxx
Sensor CPU
n
OverTemp has
transitioned to
critical from a less
severe state. (
n
=
microprocessor
number)
Error
A sensor has
changed to critical
state from a less
severe state.
1.
Make sure that the fans are
operating, that there are no
obstructions to the airflow (front
and rear of the server), that the air
baffles are in place and correctly
installed, and that the server cover
is installed and completely closed.
2.
Check the ambient temperature. You
must be operating within the
specifications (see “Server features
and specifications” on page 6 for
more information).
3.
Make sure that the heat sink for
microprocessor
n
is installed
correctly.
4.
(Trained technician only) Replace
microprocessor
n
(see “Removing a
microprocessor and heat sink” on
page 416 and “Replacing a
microprocessor and heat sink” on
page 418).
(
n
= microprocessor number)
186
System x3300 M4 Type 7382: Installation and Service Guide
Содержание System x3300 M4
Страница 1: ...System x3300 M4 Type 7382 Installation and Service Guide...
Страница 2: ......
Страница 3: ...System x3300 M4 Type 7382 Installation and Service Guide...
Страница 8: ...vi System x3300 M4 Type 7382 Installation and Service Guide...
Страница 18: ...xvi System x3300 M4 Type 7382 Installation and Service Guide...
Страница 44: ...26 System x3300 M4 Type 7382 Installation and Service Guide...
Страница 128: ...110 System x3300 M4 Type 7382 Installation and Service Guide...
Страница 156: ...138 System x3300 M4 Type 7382 Installation and Service Guide...
Страница 382: ...364 System x3300 M4 Type 7382 Installation and Service Guide...
Страница 405: ...Chapter 6 Removing and replacing components 387...
Страница 450: ...432 System x3300 M4 Type 7382 Installation and Service Guide...
Страница 454: ...436 System x3300 M4 Type 7382 Installation and Service Guide...
Страница 468: ...450 System x3300 M4 Type 7382 Installation and Service Guide...
Страница 469: ......
Страница 470: ...Part Number 00V9709 Printed in USA 1P P N 00V9709...