FusionModule1000A40 Prefabricated All-in-One Data
Center
Commissioning Guide
8 Commissioning Core Components
Issue 02 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
70
Parameter Description
Configuration
Principle
Default Value
the master device.
When the
requirement control
is
Anti-competitive
running
, the master
device synchronizes
data (the
temperature and
humidity control
type and set points
of the master device
and other
parameters) to the
slave device, and all
the smart cooling
products in the
group refer to the
mode delivered by
the master device.
When the
requirement control
is
Indoor fan
unified control
or
Central load
distribution
, all
smart cooling
product fans in the
group rotate at the
same speed.
Cascade
function
After the requirement
control is enabled, you
can configure
Cascade
function
. The cascade
function starts standby
smart cooling products
if the active one cannot
meet the refrigerating
requirements.
If the heat load to the
device increases, the
cascade function is
recommended.
Disable
Cold aisle
temperature
and
humidity
sharing
When this parameter is
enabled, the smart
cooling product, which
is not configured with
the cold aisle T/H
sensor in the group, is
logically controlled by
using the acquired
value of the configured
cold aisle T/H sensor.
This parameter can be
enabled when there are
at least two smart
cooling products in the
group are configured
with cold aisle T/H
sensors.
Disable
Hot aisle
When this parameter is
This parameter can be
Disable