FusionModule1000A40 Prefabricated All-in-One Data
Center
Commissioning Guide
8 Commissioning Core Components
Issue 02 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
92
8.4.2.2 Setting and Adding the ECC800 Collector
The requirements for ECC800 WebUI login are as follows.
Computer operating system: Windows 7 and later versions
Browser: IE11 and later versions; Firefox and later versions; Chrome and later versions
8.4.2.2.1 Setting NetEco Parameters
When the smart module can be connected to the NetEco, perform the following steps to
configure parameters.
Procedure
Step 1
Apply for a fixed IP address to the equipment room network administrator.
Step 2
Set the IP address, subnet mask, and default gateway on the ECC800 WebUI.
Table 8-13
IP parameters
Path
Parameter
Default
Value
Setting Value
System
Settings
>
System
Parameters
>
Monitor
Module
IP
>
WAN_1
IP
192.168.1.10 Set this parameter based on the IP address
assigned by the network administrator.
Subnet mask 255.255.255.
0
Set this parameter based on the subnet mask
assigned by the network administrator.
Default
gateway
192.168.1.1
Set this parameter based on the default
gateway address assigned by the network
administrator.
Step 3
Set NetEco communications parameters on the ECC800 WebUI.
Table 8-14
NetEco parameters
Path
Parameter
Default
Value
Setting Value
System
Settings
>
NMS
Application
>
NetEco
>
Communicati
on
Parameters
Server IP
192.168.8.1
1
IP address of the primary NetEco server
NOTE
The NetEco IP address and the ECC800 IP
address must be configured in the same
network to ensure normal connection
between the NetEco and the ECC800.
Port number
31220
31220
Link to the
monitoring IP
address
WAN_1
WAN_1