FusionModule1000A40 Prefabricated All-in-One Data
Center
Commissioning Guide
6 Power-On Commissioning
Issue 02 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
30
System
Check Item
Check
Sub-item
Criteria
be opened from outside the
pre-fab. module using an
access card, and door opening
operations are logged in the
management system.
The pre-fab. module door can
be opened from inside the
pre-fab. module using the exit
button, and door opening
operations are logged in the
management system.
Fire
extinguishing
system
(Standard)
Fire alarm
control panel
Indicators on the
fire alarm
control panel
Indicators on the fire alarm
control panel:
The power indicator is on.
The alarm indicator is off.
Smoke detector
Indicator
The indicator blinks once every
6s.
Heat detector
Indicator
The indicator blinks once every
6s.
Emergency
light
Power indicator
The power indicator is on.
Fire alarm
sounder
Alarm indicator
on the fire alarm
control panel
The alarm indicator is off.
Extinguishant
abort button
Pressure
Announciator
Electromagneti
c Valve
Fire Alarm
Horn
Gas Release
Indicator
Fire
extinguishing
system (CE)
Extinguishant
control panel
Indicators on the
extinguishant
control panel
Indicators on the extinguishant
control panel:
The power indicator is on.
The alarm indicator is off.
Smoke detector
Indicator
The indicator blinks once every
6s.
Heat detector
Indicator
The indicator blinks once every
6s.