FusionModule1000A40 Prefabricated All-in-One Data
Center
Commissioning Guide
8 Commissioning Core Components
Issue 02 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
96
IP Address
indicates the ECC800 login IP address.
Port
indicates the ECC800 COM2 port (3212).
Device Address
indicates the Polymer T/H sensor address.
Step 12
Click
to save the created device view.
Step 13
Choose
System
>
Configuration Management
>
Transmission Channel Management
.
Step 14
Click
Modify
after selecting the IP address of the ECC800 connected to the NMS.
If
Connection mode
is set to
Compatible
, click
Confirm
.
On the ECC800 WebUI,
Enable Security Authentication
is set to
Disable
.
If
Connection mode
is set to
Security protocol
, enter the value of
Confirm password
that has been set on the ECC800 WebUI, and click
Confirm
.
Figure 8-21
Page for managing transparent transmission channels
----End
8.4.3 Scenarios for Connecting the server
8.4.3.1 Setting SMS
This section describes how to set the interworking parameters of the SMS modem on the
NetEco. This ensures that the NetEco can communicate with the SMS modem properly and
the modem sends short messages to users properly.
Prerequisites
You have logged in to the NetEco client by web browser