FusionModule1000A40 Prefabricated All-in-One Data
Center
Commissioning Guide
8 Commissioning Core Components
Issue 02 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
69
Parameter Description
Configuration
Principle
Default Value
smart
cooling
products in
this group
cooling products in this
group (1 to 32 can be
set).
smart cooling products
in this group.
Number of
running
smart
cooling
products in
this group
Number of active units
in a group. The value
ranges from 1 to
Number of smart
cooling products in
this group
.
The host allocates
running units by smart
cooling product unit
address in ascending
order, which is from 1
to 32. The rest will
become the standby
ones.
2
Rotation
function
Disable or enable the
active and standby
smart cooling products
to change identity after
a certain time,
maximizing their
service life.
This function is
recommended when the
heat is even.
Disable
Rotation
period
Rotation days (1–30).
7 by default
7 day (s)
Rotation
time
24 hours in a day
(0–23).
0 by default
0
Forced
rotation
Forced rotation
specifies whether to
enable a forcible
rotation on the group
before the specified
rotation time. After a
forced rotation, the
accumulated time is
recalculated.
This item is set to
No
by default. If forced
rotation is required, the
function is set to
Yes
.
No
Requireme
nt control
Enable or disable the
requirement control for
the master device.
When the
requirement control
is
Disable
, the
master device does
not synchronize data
to the slave device,
and all the smart
cooling products
operate based on
their own
requirements, not
referring to the
mode delivered by
Anti-competitive
running
is
recommended for the
following scenario: In
one teamwork, the
temperature and
humidity control type
and temperature and
humidity set point of
units are the same, and
device heat loads are
distributed evenly.
Disable