Maintenance
Item
Method
Expected Result
Troubleshooting
Check the status
of power supply
and distribution
devices.
On the ECC800-
Pro WebUI, choose
Monitoring >
Power
Distribution.
The power supply
and distribution
devices are
working properly.
See the power
supply and
distribution
devices
documents.
Check the status
of the video
surveillance
system.
Enter the camera
IP address or
choose System
Settings > Video
Management on
the ECC800-Pro
monitoring system
to access the video
status.
The video
surveillance
system is working
properly.
Check the
communication
status and
communications
cable connection.
6.1.2 Monthly Maintenance
Table 6-2 Monthly maintenance for the power supply and distribution system
Maintenance
Item
Method
Expected Result
Troubleshooting
UPS power grid
environment
Check the
running status
on the UPS
LCD.
● Input voltage:
380 V AC/400 V
AC/415 V AC
(line voltage)
● Output voltage:
380 V AC/400 V
AC/415 V AC
(tolerance ±1%,
line voltage)
● If the input
voltage is
abnormal, check
the power grid
and input cable
connection.
● If the output
voltage is
abnormal, check
the UPS running
status and check
whether an
alarm is
generated.
Three-phase
power indicators
Check the
luminance of
the indicators.
The three-phase
power indicators are
bright.
Replace the
indicator that
generates no or dim
light.
FusionModule2000-S Smart Modular Data Center
User Manual
6 Operation and Maintenance
Issue 03 (2021-07-15)
Copyright © Huawei Technologies Co., Ltd.
223