Figure 4-20 Connecting rPDU cables
Step 2 Route the rPDU cables through the cable hole in the attachment plate of the side
ear and connect the cables to the AC Input1 power port on the ECC800-Pro.
Step 3 Install the rPDU cables for other IT cabinets in the same way.
----End
Follow-up Procedure
Before connecting the power plug of a device to the rPDU, loosen the locking
device on the rPDU. After connecting the power plug, tighten the locking device.
4.8 (Optional) Cabling Routes for a Smart Cooling
Product PDB
NO TE
In the precision PDF or NMW scenario, use a smart cooling product PDB to supply power to
the smart cooling product.
Cables are routed in from the top and routed out from the top or bottom of the
smart cooling product PDB.