Table 5-27 Default alarm thresholds for T/H sensors
Signal
Default Value
High temperature alarm threshold
45.0
℃
Low temperature alarm threshold
10.0
℃
High humidity alarm threshold
85.0% RH
Low humidity alarm threshold
15.0% RH
NTC1–3 high temperature alarm
threshold
35°C
NTC4–6 high temperature alarm
threshold
45°C
NTC1–3 low temperature alarm
threshold
10°C
NTC4–6 low temperature alarm
threshold
10°C
----End
5.3.11 Commissioning Cabinet Electronic Clasp Locks
When the system type is FusionModule2000 and the cabinet electronic clasp locks
are installed, perform the following steps to configure them.
Prerequisites
NO TICE
Only the electronic clasp locks of IT cabinets and smart cooling products need to
be connected to the ECC. This section describes only how to connect electronic
clasp lock cables of the IT cabinets and smart cooling products. This does not
apply to PDFs and battery cabinets.
●
The cabinet electronic clasp locks of odd- and even-numbered cabinets have
been cascaded in hand-in-hand mode respectively. One end of a network
cable is connected to the RS485_IN port on the electronic clasp lock of the
first cabinet among odd-numbered cabinets, and the other end of the cable is
connected to the COM2 port on the ECC800-Pro; one end of another network
cable is connected to the RS485_IN port on the electronic clasp lock of the
first cabinet among even-numbered cabinets, and the other end of the cable
is connected to the COM3 port on the ECC800-Pro.
●
The smart module view has been deployed.
●
The cabinet door can be opened and closed properly. If the cabinet door
cannot be opened and closed properly, adjust the position of the cabinet
electronic clasp lock by performing Steps 1 and 2.