Distribution > General Input Unit > Power Distribution Unit > Running
Parameters > Unhide All Advanced Signals > Power Distribution Settings.
----End
5.2.5 Commissioning a Smart rPDU
Prerequisites
One end of the straight-through cable has been connected to the COM port on
the rPDU and the other end has been connected to the COM port on the ECC800-
Pro or ETH converter.
Context
Table 5-11 rPDU basic information
Model
Vendor
Name Displayed
on the WebUI
Eleventh and
Twelfth
Characters in
Device Barcode
a
PDU2000-32-1PH
-20/4-M1/CLEVER
Clever
PDU2000-M(C)
FT
PDU2000-32-1PH
-20/4-M1/HPX
HPXIN
PDU2000-M(H)
6B
MD-1324-2004
Clever
rPDU-MPDU
FT
PN1-32I10-20E4G
-AV4
HPXIN
rPDU-PN
6B
ZFIF-112-0800
Clever
rPDU
FT
PN1-16X18-8E-
AH4W
HPXIN
6B
ZZIF-130-2004
Clever
FT
PN1-32I15-20E4G
-AV4W
HPXIN
6B
a: The barcode starts with 21 and is attached to the device.
The PDU2000-M(C) and PDU2000-M(H) are used as examples.
Procedure
Step 1 Set the PDU2000 monitoring parameters.
●
Set the PDU2000-M (C) monitoring parameters.
FusionModule2000-S Smart Modular Data Center
User Manual
5 Power-On Commissioning
Issue 03 (2021-07-15)
Copyright © Huawei Technologies Co., Ltd.
138