If the connection fails, check whether the cable is properly connected to
the device, whether the device is running properly, and whether the
parameter settings are consistent with the device parameters.
----End
5.3 Power-On Commissioning for the Management
System
5.3.1 Preparations and WebUI Login
Prerequisites
●
Supported operating system: Windows 7 and later versions
●
Recommended screen resolution: 1366 x 768 or higher
●
Browser: Chrome, Firefox, Internet Explorer 11 or later
Procedure
Step 1 Connect the PC network port and the WAN1 port (protected by a security
mechanism) on the ECC800-Pro using a network cable.
Table 5-13 Default IP addresses for the WAN and LAN ports on the ECC800-Pro
Port
Default IP Address
WAN1
192.168.8.10
WAN2
192.168.0.10
LAN1 and LAN2
192.168.248.10
NO TICE
● In ECC800 V100R002C10 and earlier versions, the default IP address for the
WAN1 port is 192.168.1.10.
● The WAN1 port IP address cannot be set to an IP address in any of the
following network segments: 192.168.0.x, 192.168.245.x, 192.168.246.x and
192.168.248.x.
● IP addresses for the WAN1 and WAN2 ports should not be set in the same
network segment.
● In some customized scenarios, the default IP address for the WAN2 port is
192.168.248.10. The default value may vary.
● The WAN port supports Internet access, and the LAN port supports LAN access.
Connect the PC network port to the WAN port or LAN port on the ECC800-Pro
based on the access network.
FusionModule2000-S Smart Modular Data Center
User Manual
5 Power-On Commissioning
Issue 03 (2021-07-15)
Copyright © Huawei Technologies Co., Ltd.
141