NO TICE
Before installing the camera front cover, remove the protective film from it.
Figure 3-103 Installing the front cover
----End
3.10.11 Rules for Deploying T/H Sensors
T/H sensors are deployed based on cold and hot aisles.
Procedure
Step 1 If the smart module uses cold and hot aisle containment, deploy T/H sensors on
the front and rear doors of every six IT cabinets. Smart cooling products use the
T/H sensors delivered with them.
NO TE
Components shown in the same background color belong to the same area.
Figure 3-104 Cold and hot aisle containment
Step 2 In the hot aisle containment scenario, attach the T/H sensors delivered with a
smart cooling product to the front door post of the adjacent IT cabinet.
FusionModule2000-S Smart Modular Data Center
User Manual
3 Hardware Installation
Issue 03 (2021-07-15)
Copyright © Huawei Technologies Co., Ltd.