When the temperature is low, violent impact or vibration may damage the
plastic cable sheathing. To ensure safety, comply with the following
requirements:
–
Cables can be laid or installed only when the temperature is higher than
0°C. Handle cables with caution, especially at a low temperature.
–
Cables stored at subzero temperatures must be stored at room
temperature for at least 24 hours before they are laid out.
●
Do not perform any improper operations, for example, dropping cables
directly from a vehicle.
●
When selecting, connecting, and routing cables, follow local safety regulations
and rules.
ESD
NO TICE
The static electricity generated by human bodies may damage the electrostatic-
sensitive components on boards, for example, the large-scale integrated (LSI)
circuits.
●
Wear ESD gloves or a well-grounded ESD wrist strap when touching the
device or handling boards or application-specific integrated circuits (ASICs).
●
When holding a board, hold its edge without touching any components. Do
not touch the components with your bare hands.
●
Package boards with ESD packaging materials before storing or transporting
them.
Figure 1-1 Wearing an ESD wrist strap
Neutral-Ground Voltage
It is recommended that the three-phase loads be equalized and the neutral-
ground voltage be kept at less than 2 V to meet power distribution requirements.
FusionModule2000-S Smart Modular Data Center
User Manual
1 Safety Information
Issue 03 (2021-07-15)
Copyright © Huawei Technologies Co., Ltd.
6