Procedure
Step 1 Open the rear door of the cabinet.
Step 2 Connect the IT load of the faulty rPDU to a normal rPDU.
Step 3 Turn off the upstream power distribution switch for the faulty rPDU. Ensure that
the rPDU input has no power, and then remove the power cables from the
terminal block on the top of the rPDU.
Step 4 Remove the bolts that secure the rPDU using a Phillips screwdriver.
Step 5 Secure the new rPDU in the installation position of the old rPDU.
Step 6 Connect the input power cables to the rPDU.
Step 7 Turn on the upstream power distribution switch for the rPDU and the rPDU input
switch.
Step 8 Verify that the rPDU power output is normal and then connect the IT load cables
to the rPDU.
----End
6.3.8 Replacing a Smart rPDU
Impact on the System
One power input of the equipment cannot work.
Preparations
●
Tools: Phillips screwdriver, step ladder, label, marker
●
Material: smart rPDU of the same specifications
Context
The smart rPDU is installed near the rear door of the cabinet.
Procedure
Step 1 Open the rear door of the cabinet.
Step 2 Connect the IT load of the faulty smart rPDU to a normal rPDU.
Step 3 Turn off the industrial connector for the faulty smart rPDU. Ensure that the smart
rPDU input has no power.
Step 4 Remove signal cables from the ports on the smart rPDU and label the cables.
Step 5 Remove the screws that secure the smart rPDU using a Phillips screwdriver.
Step 6 Secure the new smart rPDU in the installation position of the old smart rPDU.
Step 7 Connect the input power cables and signal cables to the new smart rPDU.
Step 8 Turn on the upstream power distribution switch for the smart rPDU and the smart
rPDU input switch.