Item
200 kVA
300 kVA
400 kVA
500 kVA
Equipote
ntial
ground
point
Recommended
cross-sectional
area (mm
2
)
16
Table 6-3 Recommended power cable cross-sectional areas (600–800 kVA)
Item
600 kVA
700 kVA
800 kVA
Mains input
Mains input current (A)
1115
1300
1486
Recommended
cross-sectional
area (mm
2
)
L1
4 x 185
4 x 240
4 x 240
L2
4 x 185
4 x 240
4 x 240
L3
4 x 185
4 x 240
4 x 240
N
4 x 185
4 x 240
4 x 240
PE
240
240
240
Bypass input
Bypass input current (A)
912
1064
1215
Recommended
cross-sectional
area (mm
2
)
L1
4 x 185
4 x 240
4 x 240
L2
4 x 185
4 x 240
4 x 240
L3
4 x 185
4 x 240
4 x 240
N
4 x 185
4 x 240
4 x 240
PE
240
240
240
Output
Output current (A)
912
1064
1215
Recommended
cross-sectional
area (mm
2
)
U
4 x 185
4 x 240
4 x 240
V
4 x 185
4 x 240
4 x 240
W
4 x 185
4 x 240
4 x 240
N
4 x 185
4 x 240
4 x 240
PE
240
240
240
Battery input
(lead-acid
battery)
Nominal battery
discharge current (A)
1330
1551
1773
Maximum battery
discharge current (A)
1593
1858
2123
Recommended
cross-sectional
area (mm
2
)
+
4 x 185
4 x 240
4 x 240
-
4 x 185
4 x 240
4 x 240
PE
240
240
240
UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Module)
6 Installation
Issue 02 (2021-04-22)
Copyright © Huawei Technologies Co., Ltd.
64