Pin
Description
2
RS485_T–
3
-
4
5
RS485_R–
6
GND
7
-
8
-
NO TE
If cables are prepared onsite, follow the three methods below:
● Connect pin 1 and pin 2. Pin 1 connects to RS485+ and pin 2 connects to RS485–.
● Connect pin 4 and pin 5. Pin 4 connects to RS485+ and pin 5 connects to RS485–.
● Connect pins 1, 2, 4, and 5. Twist cables to pin 1 and pin 4 into one cable and then
connect it to RS485+. Twist cables to pin 2 and pin 5 into one and then connect it to
RS485–.
4.4 MDU
The MDU allows you to control UPS operations, view the running status and
alarms, and set parameters. For details, see the
UPS5000 Monitoring Module User
Manual
.
Dimensions (H x W x D): 175 mm x 264 mm x 40 mm
Figure 4-14 Appearance
(1) Status indicator
(2) LCD touchscreen
UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Module)
4 Component Description
Issue 02 (2021-04-22)
Copyright © Huawei Technologies Co., Ltd.
41