NO TICE
● This is a category C3 UPS product for commercial and industrial application in
the second environment − installation restrictions or additional measures may
be needed to prevent disturbances.
● After unpacking the UPS, you are advised to power on the UPS as soon as
possible. If you temporarily do not use the UPS, take appropriate measures to
prevent moisture, dust, and foreign matter from entering the UPS.
● After unpacking batteries, you are advised to connect the battery supply as
soon as possible. If you temporarily do not use the batteries, store them in a
dry and clean environment. If batteries are stored for more than 90 days,
charge them in time. Otherwise, the battery lifespan may be affected.
● Install the UPS in an area far away from liquids. Do not install it under areas
prone to water leakage, such as air conditioner vents, ventilation vents, or
feeder windows of the equipment room. Ensure that no liquid enters the UPS
to prevent short circuits. Ensure that there is no condensation inside the
equipment or equipment room.
● If any liquid is detected inside the equipment, immediately disconnect the
power supply and contact the administrator.
D ANGER
● Do not expose the equipment to flammable or explosive gas or smoke. Do not
perform any operation on the equipment in such environments.
● During installation and maintenance, ensure that sundries do not enter the
UPS. Otherwise, equipment damage, load power derating, power failure, and
personal injury may occur.
If the valid mains voltage exceeds 320 V AC, the UPS may be damaged.
A UPS can be used to serve resistive-capacitive loads, resistive loads, and micro-
inductive loads. It is recommended that a UPS not be used for pure capacitive
loads, pure inductive loads, and half-wave rectification loads. A UPS does not
apply to regeneration loads.
Any operation on any electrical device in an environment that has inflammable air
can cause extreme danger. Strictly obey the operating environmental requirements
specified in related user manuals when using or storing the device.
The UPS can be configured with a backfeed protection dry contact to work with
an external automatic circuit breaker, preventing the voltage from flowing back to
input terminals over static bypass circuits. If the installation and maintenance
personnel do not need backfeed protection, paste labels on external mains and
bypass input switches, informing that the UPS is connected to a backfeed
protection card. Disconnect the backfeed protection card from the UPS before
operating the UPS.