Silk Screen
Signal Description
Status
Description
Initial
Status
SWITCH
STATUS_MT
Port for monitoring the
maintenance switch
● Open: The
maintenance
switch is ON.
● Closed: The
maintenance
switch is OFF.
Open
a
SWITCH
STATUS_0V
Port for signal ground
SWITCH
STATUS_BP
Port for monitoring the
bypass input circuit breaker
● Closed: The
bypass input
circuit breaker
is ON.
● Open: The
bypass input
circuit breaker
is OFF.
Closed
a
SWITCH
STATUS_0V
Port for signal ground
SPD
Port for monitoring the
input AC SPD
● Closed: The
input AC SPD is
normal.
● Open: The input
AC SPD fails.
Closed
a
0V
Port for signal ground
a: On the LCD, choose System Info > Settings > System Settings > Dry
Contact Set > MUE05A DI type configure, and customize the initial status of
Battery ground fault [BTG], D.G. connection [GEN], PDC output breaker
[OUT], PDC maintenance breaker [MT], BP/SYSMT switch, and SPD/SYSOUT
switch.
4.3.4 Monitoring Interface Card
The monitoring interface card provides external ports as well as monitoring and
control functions for the MDU. The monitoring interface card provides the
ambient temperature and humidity sensor port, FE port, battery temperature
monitoring port, and network management port. The MDU monitors the UPS,
allows users to set parameters, delivers commands, reports system information,
and displays key UPS information and parameters on the LCD.