NO TE
If MUE06A connection is set to Enable and the backfeed protection card fails to
communicate with the UPS, the system reports a Dry contact board fault alarm.
----End
7.1.8 (Optional) Setting the Intelligent Detection Card
Prerequisites
An intelligent detection card is installed.
Procedure
Step 1 On the LCD, choose System Info > Settings > System Settings and set
Intelligent detection module to Enable.
----End
7.2 Shutting Down and Powering Off the UPS
Context
NO TICE
If the bypass is normal, the UPS transfers to bypass mode after the inverter is shut
down; if the bypass is abnormal, the UPS supplies no power after the inverter is
shut down. Before shutting down the UPS, ensure that all loads have been shut
down.
Procedure
Step 1 Shut down the inverter.
●
Shutting down the inverter on the LCD
Choose Common Functions > Inv. OFF. After confirmation, the inverter is
shut down.
NO TE
You can also choose System Info > Maintenance > Inv. OFF to shut down the
inverter.
●
Shutting down the inverter on the WebUI
Choose Monitoring > UPS System > Running Control, and click Inv. OFF.
If the inverter shuts down and the bypass is normal, the UPS transfers to bypass
mode. The Bypass mode alarm is displayed on the LCD.