Item
600 kVA
700 kVA
800 kVA
Battery input
(SmartLi)
Nominal battery
discharge current (A)
1234
1439
1645
Maximum battery
discharge current (A)
1547
1806
2064
Recommended cross-
sectional area
For details, see the IEC-60364-5-52 specifications and
SmartLi User Manual
.
Equipotential
ground point
Recommended cross-
sectional area (mm
2
)
16
NO TE
The rated voltage of the SmartLi is 512 V. The voltage is 408 V at the maximum discharge
current.
●
The currents listed in the table are measured at a rated voltage of 380 V.
●
When selecting, connecting, and routing power cables, follow local safety
regulations and rules.
●
When the external conditions such as the cable layout or ambient
temperatures change, perform verification in accordance with the IEC
60364-5-52 or local regulations.
●
For the 400 V rated voltage, multiply the current by 0.95.
●
For the 415 V rated voltage, multiply the current by 0.92.
●
When the primary loads are non-linear loads, increase the cross-sectional
areas of the neutral wires to 1.5–1.7 times.
●
The nominal battery discharge current refers to the current of forty 12 V
batteries at 480 V in standard configuration.
●
The maximum battery discharge current refers to the current when forty 12 V
batteries in standard configuration, that is, two hundred and forty 2 V battery
cells (1.67 V/cell), stop discharging.
●
The battery cable specifications are selected based on 40 batteries by default
and compatible with application scenarios with 30–50 batteries.
●
When the mains input and bypass input share a power source, configure
mains input power cables as input power cables. In addition, cables
recommended in the table apply only when the following requirements are
met:
–
Routing mode: The cables are routed over a tray or bracket in a single
layer (E in IEC 60364-5-52). The distance between cables should be
greater than twice the cable diameter. Routing mode: The cables are
routed over a tray or bracket in a single layer (E multi-core and G single-
core in IEC 60364-5-52).
–
The ambient temperature is 30°C.
–
The AC voltage loss is less than 3%, and the DC voltage loss is less than
1%.
UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Module)
6 Installation
Issue 02 (2021-04-22)
Copyright © Huawei Technologies Co., Ltd.