Procedure
Step 1 Clear the EPO state of the system. Check that the external EPO switch connected
to the dry contact is in non-EPO state or insert the 4-pin terminal on the EPO port
of the dry contact card.
Step 2 Clear the EPO alarm.
●
On the LCD
Choose System Info > Alarms and tap Clear Faults. After confirmation, the
EPO alarm is cleared.
●
On the WebUI
Choose Monitoring > UPS System > Running Control > System Commands
and Tests and click Clear Faults. The EPO alarm is cleared.
Step 3 View active alarms and check that the EPO alarm is cleared. If the system bypass
input is normal, the UPS transfers to bypass mode.
●
On the LCD
Choose System Info > Alarms > Active Alarms to check that the EPO alarm
has been cleared.
●
On the WebUI
Choose Home > Active Alarm to check that the EPO alarm has been cleared.
Step 4 Start the inverter.
----End