Item
400 kVA/500 kVA/600 kVA/800 kVA
Battery string
sharing
(lead-acid
battery)
● Lead-acid battery: Battery string sharing is supported in a
parallel system. No battery is shared by default.
● SmartLi 2.0: Battery string sharing is supported. When
multiple UPSs are connected in parallel, the lithium battery
cabinet can be expanded for half a cabinet. No battery is
shared by default.
Charging
voltage
(lead-acid
battery)
● Default equalized charging voltage: 2.35 V/cell
● Default float charging voltage: 2.25 V/cell
Battery type
● VRLA
● SmartLi
NO TICE
The UPS supports the SmartLi. For details about the parameters, see the
SmartLi
User Manual
.
Table 11-8 Output electrical specifications
Item
400 kVA/500 kVA/600 kVA
800 kVA
Power
system
Three-phase four-wire + PE
Voltage
380 V AC/400 V AC/415 V AC (line voltage)
Frequency
● In normal mode, the frequency is synchronous with the
bypass input frequency.
● In battery mode, the frequency is 50 Hz/60 Hz with a
tolerance of ±0.05%.
Voltage
distortion
● Linear load: THD < 1% (380 V/400 V/415 V, 50–100%
balanced load)
● Non-linear load: THD < 3% (380 V/400 V/415 V, 50–100%
balanced load)
Power factor 1
Transfer time Uninterruptible transfer: 0 ms; interruptible transfer: ≤ 5 ms
Output
voltage
imbalance
Voltage imbalance: ±1%
Phase imbalance: 120±1° (balanced load and unbalanced load)
UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Module)
11 Technical Specifications