UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
4 User Interface
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
199
Item
Description
battery
string
CIM
logical
start addr
Specifies the communication address when the northbound device queries
CIM data. The value range is 0 to 124. The default value is 0.
Advanced Param.
screen.
Figure 4-58
Advanced Parameters
Item
Description
Current
source
Specifies the specifications of the Hall effect sensor used to detect CIM
current. The default value is
Hall sensor 200A
.
BCB
connects
to CIM
Specifies whether the BCB connects to the CIM. The default value is
Disable
.
Batt.
abnormal
BCB trip
Specifies whether BCB trips when batteries are abnormal. The default value
is
Disable
.
Multi-Hal
l cur.
setting
Multi-Hall cur. setting
is equal to the number of Hall effect sensors at the
positive or negative terminal of a battery string (
Multi-Hall cur. setting
≥ 1).
The default value is
1
.
shows the battery string config screen. On this screen, the CIM No. and BIM
No. can be set under each battery string.