UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
4 User Interface
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
185
Item
Description
When the voltage level is 380 V, the value range is 10%, 15% (default), 20%, and
25%.
When the voltage level is 400 V, the value range is 10%, 15% (default), and 20%.
When the voltage level is 415 V, the value range is 10% (default) and 15%.
Minimum
bypass
voltage
When the difference between the bypass voltage and the rated voltage
exceeds the lower threshold for the bypass voltage, the system determines
that the bypass voltage is abnormal and that the bypass is unavailable. The
value can be –10%, –15%, –20%, –30%, –40%, –50%, or –60%. The default
value is –20%.
ECO
voltage
range
In ECO mode, when the difference between the bypass voltage and the rated
voltage is greater than this value, the system determines that the ECO
voltage is abnormal and transfers to normal mode. The values can be ±5%,
±6%, ±7%, ±8%, ±9%, or ±10%. The default value is ±5%.
BPM mode
upon BPM
overtemp.
Specifies whether to start bypass mode when overtemperature occurs. The
default value is
Enable
.
Battery Parameter Settings
Battery parameter settings impact battery maintenance, battery lifespan, and UPS discharge
time. When you set battery parameters, note the following: