UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
2 Overview
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
30
Indicator
Color
Status
Description
and off for 2.5s).
Blinking at short
intervals
The module is not configured, the
inverter or rectifier DSP software
is being upgraded, or the inverter
CPLD software is being upgraded
(blinking at 4 Hz, on for 0.125s
and off for 0.125s).
Off
The rectifier CPLD software is
being upgraded.
Alarm indicator
Yellow
Steady on
A minor alarm is generated for the
inverter or rectifier.
Off
There is no minor alarm for the
inverter or rectifier, or the rectifier
CPLD software is being upgraded.
Fault indicator
Red
Steady on
A critical alarm is generated for
the inverter or rectifier.
Off
There is no critical alarm for the
inverter or rectifier, or the rectifier
CPLD software is being upgraded.
Functions
The power module consists of a power factor correction (PFC) rectifier, inverter, and DC/DC
converter. The power module performs AC/DC or DC/DC conversion on the mains and
battery inputs, and stabilizes the bus voltage. The inverter (DC/AC) converts the inputs into
sine wave outputs.
Specifications
Dimensions (H x W x D): 130 mm x 442 mm x 620 mm
Weight: ≤ 35 kg
Rated output capacity: 50 kVA/50 kW
Power density: 50 kVA/3 U
2.3.4 Bypass Module
Appearance
400 kVA/500 kVA/600 kVA bypass module have the same appearance.
600 kVA bypass module.