UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
4 User Interface
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
178
Item
Description
ambient
temperature
alarm
threshold
(°C)
the threshold specified by this parameter. The value range is 40 to 60. The
default value is
55
.
Low
ambient
temperature
alarm
threshold
(°C)
An alarm is generated when the ambient temperature is lower than the
threshold specified by this parameter. The value range is –20 to 0. The
default value is
–10
.
Top outlet
fan
Enable this parameter if a top outlet fan is configured. Then the fan
running status can be checked. The default value is
Disable
.
EOD restart
If the mains is not functioning normally, the UPS will transfer to battery
mode. When batteries reach the EOD threshold, the bypass is disabled, and
EOD restart
is enabled, the UPS will restart as soon as the mains resumes.
If
EOD restart
is disabled, clear the alarm manually or enable the restart
function for the UPS.
This function is enabled by default.
Figure 4-35
Advanced Param. screen 3
Item
Description
EOD restart
delay (min)
If
EOD restart
is set to
Enable
, the UPS starts working after
EOD
restart delay
when the mains recovers from an EOD power failure. The
value range is 1–1440 min, and the default value is 10 min.
Inverter
async. alarm
Specifies whether an
Inverter asynchronous
alarm can be displayed on
the LCD when the inverter cannot track the bypass frequency change.
Normal power supply is not affected no matter whether this parameter is
set to
Enable
or
Disable
. The default value is
Disable
.