UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
4 User Interface
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
214
Figure 4-80
Param. Settings page
Calib. output current if no load
Calib. output current if no load
can be used only when the UPS output carries no load. If
this parameter is changed from
Disable
to
Enable
, the UPS will automatically calibrate the
no-load output current and load rate once. If this parameter is changed from
Enable
to
Disable
, the UPS will not automatically perform calibration and the UPS operation will not be
affected.
4.2.2.4 Comm. Config. Page
Open the
Comm. Config.
page to set communications information. See
Figure 4-81
Comm. Config. page
4.2.2.5 CIM Parameters
Open the
CIM Param.
Screen to set basic parameters, advanced parameters, and battery
string configurations, as shown in