UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
4 User Interface
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
181
Item
Description
e period (d)
Battery
segment
detection
Specifies whether the alarm is enabled. An alarm is generated only when the
alarm is enabled and the alarm generating conditions are met. The default
value is
Enable
.
Batt.
charging
capacity
mismatch
After this function is enabled, an alarm is generated if the configured battery
capacity exceeds the charging capacity of the rack. The default value is
Enable
.
EPO
detection
Indicates whether to enable emergency power-off (EPO). EPO is performed
only when this parameter is enabled and the EPO switch is triggered. This
function is enabled by default.
Figure 4-38
Advanced Param. screen 6
UPS model
should be set by professional technical personnel of Huawei or personnel authorized by
Huawei.
Item
Description
Lightload BPM cur.
eql. Detect
Enable or disable the light load bypass current imbalance alarm. If
this parameter is set to
Enable
, the load is light (less than 30%
load), and the load rate of a certain rack is less than 10%, the
system will generate a bypass current imbalance alarm and cannot
enter the ECO mode. If this parameter is set to
Disable
, the
preceding detection is not performed. Whether the bypass current
is imbalanced does not affect the ECO bypass mode. The default
value is
Enable
.
RAM verification
Enable or disable the memory check function. If this parameter is
set to
Enable
, the control chip RAM working status is checked
regularly. If this parameter is set to
Disable
, regular check is
disabled.