UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
5 Operations
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
239
After you set network parameters, connect the UPS to the network over a network cable, which
enables you to remotely manage the UPS. If you do not need remote management, retain the default
network parameter settings.
Table 5-2
Battery parameter setting example
Battery
Specifications
Number of
Batteries
Number of
Battery
Strings
Number of
Cells
Battery
Capacity
150 Ah/12 V
36 batteries in
series
Two battery
strings
connected in
parallel
36 x 6 = 216
150 Ah + 150
Ah = 300 Ah
300 Ah/2 V
192 batteries in
series
Two battery
strings
connected in
parallel
192 x 1 = 192
300 Ah + 300
Ah = 600 Ah
300 Ah/12 V
40 batteries in
series
Three battery
strings
connected in
parallel
40 x 6 = 240
300 Ah + 300
Ah + 300 Ah =
900 Ah
300 Ah/2 V
240 batteries in
series
Four battery
strings
connected in
parallel
240 x 1 = 240
300 Ah + 300
Ah + 300 Ah +
300 Ah = 1200
Ah
Step 2
After you set parameters on the
Settings Wizard
screen, the MDU displays the
Bypass mode
and
No battery
alarms, which do not need to be handled. If there is any other alarm, you need
to rectify the fault.
If dry contact signals are connected to the system, choose
System Info
>
Settings
>
Dry contacts
and
check that the connected dry contacts have been enabled and that the disconnected dry contacts have
been disabled.
Step 3
View the system running diagram on the MDU to check that the UPS is working in bypass
mode.
----End