UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
4 User Interface
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
172
Communications Settings
Figure 4-29
Communication screen 1
IP address allocation
If the MDU is directly connected to a computer, the IP address can only be allocated
manually. The IP addresses of the MDU and computer must be in the same network
segment, and must be different.
If the MDU is connected to a computer through a LAN switch or router with the DHCP
function, the IP address can be allocated manually or automatically. Manual allocation is
used by default.
−
Manual
: Check that their IP addresses are two different values on the same network
segment. Set the UPS IP address to be in the same subnet as the PC IP address.
Perform the bitwise AND operation for the UPS IP address and the PC IP address
with the subnet mask respectively. If the operation results are the same, the two IP
addresses are in the same subnet.
AND operation rule: 1 AND 1 = 1, 1 AND 0 = 0, 0 AND 1 = 0, 0 AND 0 = 0. That
is when the corresponding bits are both 1, the result is 1. In other cases, the result is
0.
Table 4-3
Bitwise AND operation example
-
PC IP address
(182.98.225.125)
UPS IP address
(182.98.225.112)
PC IP address/UPS IP
address
10110110.01100010.111000
01.01111101
10110110.01100010.111000
01.01110000
Subnet mask
(255.255.255.192)
11111111.11111111.111111
11.11000000
11111111.11111111.111111
11.11000000
Bitwise AND operation
result
10110110.01100010.111000
01.01000000
10110110.01100010.111000
01.01000000
−
Automatic
: The MDU automatically searches for available IP addresses in the
connected network. Ensure that the MDU and PC are on the same network segment.