UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
3 Installation
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
84
Mounting
Fitting
Number of
Fittings
Screw
Specifications
Number of
Bolts (PCS)
Torque
(N·m)
Remarks
strip
cables.
Middle
connecting
plate
2
M6x30
4
3
Installed on the cabinet
before delivery.
Step 1
Use a pallet truck to move the power cabinets and bypass cabinets to the mounting holes for
the cabinets with the power cabinets on the left and the bypass cabinets on the right. Align the
cabinets.
Use a pallet truck to adjust the position of the bypass cabinets to align the front doors of the bypass
cabinets with the front doors of the power cabinets.
Step 2
Open the front doors of the power cabinets and bypass cabinets.
Step 3
Install the connecting plates between the bypass cabinet and its adjacent power cabinet based
on the following sequence: bottom, top, and middle connecting plates.
Figure 3-33
Installing connecting plates
Step 4
Use M12x60 expansion bolts to secure the cabinets to the expansion bolt holes on the ground.