UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
8 Technical Specifications
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
281
Item
400 kVA
500 kVA
600 kVA
800 kVA
voltage
Rated
frequency
50 Hz or 60 Hz
Input
frequency
±6 Hz (adjustable, 0.5–6 Hz, ±2 Hz by default)
Input system
The mains input and bypass input can share a power source or use different
power sources.
8.7 Battery Specifications
Item
400 kVA
500 kVA
600 kVA
800 kVA
Battery voltage
360–528 V DC (12 V batteries, 30–44 batteries, 40 by default); If there
are 36–44 batteries, output power is not derated. If there are 34 batteries,
output power is derated to 0.9. If there are 32 or 30 batteries, output
power is derated to 0.8.
Battery
management
Intelligent battery management
One-button
cold start
In the case of a mains failure, batteries can start the UPS to power loads.
Battery string
sharing
Battery string sharing is supported in a parallel system. No battery string
is shared by default.
Charge voltage
Equalized voltage: 2.3–2.4 V/Cell, default: 2.35 V/Cell (30–42
batteries)
Equalized voltage: 2.3–2.35 V/Cell, default: 2.35 V/Cell (44
batteries)
Float voltage: 2.23–2.3 V/Cell, default: 2.25 V/Cell (30–44 batteries)
8.8 Output Electrical Specifications
Item
400 kVA
500 kVA
600 kVA
800 kVA
Output system
Three-phase, four-wire, and PE
Voltage
380 V AC, 400 V AC, or 415 V AC (tolerance ± 1%) (line voltage)
Frequency
In normal mode, the mains frequency is synchronous with the
bypass input frequency.
In battery mode, the frequency is 50 Hz or 60 Hz (tolerance