UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
5 Operations
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
263
Figure 5-32
EPO ports
After you press the EPO button, the
EPO
and
No power supplied
alarms are displayed on the
LCD.
5.10 Clearing the EPO State
Procedure
Step 1
Clear the EPO state. Ensure that the EPO button connected to the dry contact is not in the
EPO state.
Step 2
Clear the EPO alarm.
On the LCD
On the LCD, choose
System Info
>
Alarms
and tap
Clear Faults
. In the displayed
dialog box, tap
Yes
. The EPO alarm is cleared successfully.
Figure 5-33
Clearing faults
On the WebUI
Choose
Monitoring
>
Control
>
System Commands and Tests
and click
Clear Fault
.
The EPO alarm is cleared successfully.