UPS5000-E-(350 kVA-800 kVA)
User Manual (50 kVA Power Modules)
4 User Interface
Issue 05 (2018-01-08)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
198
Figure 4-56
Basic Parameters 1
Figure 4-57
Basic Parameters 2
Item
Description
Number
of CIMs
A maximum of four CIMs are supported and the default value is 0.
CIM start
address
The CIM start address cannot be changed. The DIP switch should be set to
0000 for the first CIM, and the DIP switch setting for a later connected CIM
should increase by 1 (binary) than that set for the previous CIM.
CIM
Number
of BIMs
Specifies the number of BIMs managed by the CIM. The value range is 0 to
300. The default value is 0.
Number
of battery
strings
Specifies the number of battery strings connected in parallel. The value range
is 0 to 4. The default value is 0.
Batteries
in a single
Specifies the number of batteries in a battery string. The value range is 0 to
300. The default value is 0.